|
4. TANK ATTACHMENTS
4.1 U-VENTS
4.1.1 Standard u-vents are constructed from PVC or CPVC
and are provided with a loose male adapter. This allows the u-vent to be cut to the desired height. A threaded
or solvent welded socket fitting can be used. U-vents can be purchased with an optional bug screen insert (CPVC
and fiberglass materials) installed.
4.1.2 When installing the u-vent in a solvent weld socket
fitting, solvent weld the u-vent with the proper solvent cement in the desired position into a previously installed
fitting. If the u-vent is to be used in a threaded fitting, solvent weld the male adapter provided to the u-vent
and install the u-vent assembly into a previously installed threaded fitting. Refer to Figure 4.1 for an exploded
illustration of this as-sembly.

Figure 4.1
4.2 DOWN PIPES
(TANK FITTING SUPPORTED) -EXTERNAL AND/ OR INTERNAL
4.2.1 Down pipes are shipped loose and have been cut to
size to meet customer specifications. All down pipes shall be supported at 5 ft. maximum intervals with the support
structures provided.
4.2.2 Assemble the piping loosely using Figure 4.2, the
guidelines detailed below, and the customer approved tank drawing to ensure all parts are present and cut to meet
the customer's requirements. As soon as all parts have been checked, assemble the parts with solvent weld cement
and/ or threaded connections as shown in Figure 4.2.
4.2.3 Assemble and install support structures as shown in
Figure 4.2 (without the saddle clamp cover caps and clips). Make sure the support clamp orientation is correct
(with the small width of the wedge toward the top of the tank) and that the plugged support pipes are installed
with the plugged end as close to the support fitting as possible. Assemble and install piping as per the customer
approved drawing. As piping is being installed on the tank, lock it in place with the saddle clamp cover caps and
clips provided (make sure that the sealing o-ring is in the proper position as the pipe is po-sitioned into the
saddle support body). Seal all threaded pipe connections with Teflon 7 pipe sealant and connect solvent weld sockets
with solvent cement.

Figure 4.2
4.3 DOWN PIPES
(WELDED BOSS SUPPORTED) -EXTERNAL AND/ OR INTERNAL
4.3.1 Down pipes are shipped loose and have been cut to
size to meet customer specifications. All down pipes shall be supported at 5 ft. maximum intervals with the support
structures provided.
4.3.2 Assemble the piping loosely using Figure 4.3, the
guidelines detailed below, and the customer ap-proved tank drawing to ensure all parts are present and cut to meet
the customer's requirements. As soon as all parts have been checked, assemble the parts with solvent weld cement
and/ or threaded connections as shown in Figure 4.3.
4.3.3 Assemble and install support structures as shown in
Figure 4.3 (without the saddle clamp cover caps and clips). Since the support fitting does not penetrate the tank
wall, the threaded connection to the support fitting does not need pipe sealant. Make sure the support clamp orientation
is correct (with the small width of the wedge toward the top of the tank). Assemble and install piping as per the
customer approved drawing. As piping is being installed on the tank, lock it in place with the saddle clamp cover
caps and clips provided (make sure that the sealing o-ring is in the proper position as the pipe is positioned
into the saddle support body). Seal all threaded pipe connections (except the support fittings) with Teflon 7 pipe
sealant and connect solvent weld sockets with solvent cement.

Figure 4.3
4.4 DOWN PIPES
(WELDED PE SUPPORTED) -EXTERNAL AND/ OR INTERNAL
4.4.1 Down pipes are shipped loose and have been cut to
size to meet customer specifications. All down pipes shall be supported at 5 ft. maximum intervals with the support
structures provided.
4.4.2 Assemble the piping loosely using Figure 4.4, the
guidelines detailed below, and the customer ap-proved tank drawing to ensure all parts are present and cut to meet
the customer's requirements. The piping should be inserted into the holes in the welded support structures prior
to installing the fitting in the tank. As soon as all parts have been checked, assemble the parts with solvent
weld cement and/ or threaded connections as shown in Figure 4.4. Seal all threaded pipe connections with Teflon
7 pipe sealant and connect solvent weld sockets with the correct type of solvent cement.

Figure 4.4
4.5 DOWN PIPE
-INDEPENDENTLY SUPPORTED -(EXTERNAL ONLY)
4.5.1 Down pipes are shipped loose and have been cut to
size to meet customer specifications. All down pipes shall be supported at 42 in. maximum intervals with the support
clamps provided.
4.5.2 Assemble the piping loosely using Figure 4.5, the
guidelines detailed below, and the customer ap-proved tank drawing to ensure all parts are present and cut to meet
the customer's requirements. Mark the strut post base on the concrete when in proper position. Install 2 ea. 3/
8" adhesive anchors and bolt base into position. As soon as all parts have been checked, assemble the parts
with solvent weld cement and/ or threaded connections as shown in Figure 4.5.
4.5.3 Assemble and install support structures as shown in
Figure 4.5. Make sure the support clamps are spaced evenly. Locate the strut catchers and twist 90° to lock
in place. Install the clamps to the strut catchers with the #10 screws provided. Clamps 3 in. and larger require
2 ea. strut catchers, #10 screws and #10 washers. The pipe will click into position in the clamps. Make sure all
clamps have clicked to full engagement and are tight. Assemble and install piping as per the customer approval
drawing. Seal all threaded pipe connections with Teflon 7 pipe sealant and connect solvent weld sockets with solvent
cement.

Figure 4.5
4.6 FLEXIBLE
SIGHT LEVEL GAGES USE ORIFICE SPACER ON DOUBLE WALL TANK ASS'Y.
4.6.1 Sight level gage assemblies are shipped loose and
have been cut to size to meet customer specifi-cations. Sight gages may be ordered with either no valve, 1, 2,
or 3 valves. Please refer to the customer approved drawing to determine the number of valves required.
4.6.2 Using the assembly drawings shown in Figure 4.6, verify
that all parts are present and assemble the unit per the appropriate drawing. Seal all threaded pipe connections
with Teflon 7 pipe sealant. Gallonage decals may be purchased as separate items and customer applied to the tank
to assist in in-dication of tank gallonage. NOTE -Gallonage decals are not available for all tank sizes.
4.7 REVERSE LEVEL
SIGHT GAGE
4.7.1 The component parts (except the rope) have been cut
to meet Sierra Sales and customer specifications. The sight gage shall be supported at 5 ft. maximum intervals
to the liquid holding tank with the support structures provided.
4.7.2 Assemble the piping loosely using Figure 4.7, the
guidelines detailed below, and the customer approved tank drawing to ensure all parts are present and cut to length.
As soon as all parts have been checked, assemble the parts with solvent weld cement and/ or threaded connections
as shown in Figure 4.7. NOTE -Do not use solvent weld cement on the outside joints indicated in Figure 4.7. SII
recommends periodic inspection of the rollers in the tee assemblies and the rope to ensure proper operation of
the gage.

Figure 4.6
4.7.3 Assemble and install the support structures as shown
in Figure 4.7 (without the saddle clamp cover caps and clips). Make sure the support clamp orientation is correct
(with the small width of the wedge toward the top of the tank) and that the plugged support pipes are installed
with the plugged end as close to the support fitting as possible. Make sure that the indicator board has been installed
over the outer pipe supports as shown in Figure 4.7. Assemble and install piping as per the customer approved drawing.
As piping is being installed on the tank, lock it in place with the saddle clamp cover caps and clips provided
(make sure that the sealing o-ring is in the proper posi-tion as the pipe is positioned into the saddle support
body). Seal all threaded pipe connections with Teflon 7 pipe sealant and connect solvent weld sockets with the
correct solvent ce-ment (except the joints as noted in Figure 4.7).
4.7.4 With the inner and outer tank pipes in place, connect
the rope provided to the tank float (This is accomplished by threading the rope through the center hole in the
float and out one of the side holes, double knotting the rope, cutting off any excess material and pulling the
rope back so the knot holds under the center hole.) and lower it into the inner pipe as shown. Thread the rope
through the tee assemblies and the connecting pipe as shown. At this point the float should be at the bottom of
the tank, the tee assemblies and connecting pipe should be assembled and sitting off at an angle from the outer
clear 2" PVC pipe. With the rope threaded through the outer tee assembly, attach the rope to the indicator
in a position parallel with the zero mark on the indicator board. (This is accomplished by threading the rope through
the center hole in the indicator, double knotting the rope, checking the indicator position, adjusting as necessary
and cutting and excess material protruding from the bottom of the indicator.) Put the indicator into the outer
clear 2" PVC pipe while swinging the tee assemblies and connecting pipe into position. With all piping and
tee assemblies installed, install the 3" PVC pipe plugs. During the tank hydrotest and first operations of
the tank, check the gage for proper level indication and adjust as necessary. NOTE -This is a gallonage indicator
and is not intended as an accurate measuring device.

Figure 4.7
4.8 ULTRASONIC
LEVEL INDICATOR
4.8.1 Install the PE bulkhead fitting per section 3.1 for
sensors with male pipe threads. Install the sensor into the fitting with Teflon ® pipe sealant. Remove the
display unit box cover. Attach the display unit to the PE mounting plates provided on the tank with 4 ea. #10 S.
S. Self-tapping screws. Attach the sensor cable to the control box with small strain relief and connect wires per
label in the box. Attach the unit to 110 VAC and test unit. The display unit is preprogrammed for the tank ordered.
The display with show hundreds of gallons (display x 100 = gallons). Refer to literature shipped with unit to answer
any additional questions.
4.9 LEAK DETECTOR
UNIT (FOR USE WITH SIERRA SALES CONTAINMENT TANKS ONLY)
4.9.1 The leak detector unit consists of a proximity sensor,
2 in. FPT fitting connection, 2 in. bung plug, ¾ in. strain relief, and an indicator box. Install the ¾
in. strain relief into the 2 in. bung plug. Loosely install the proximity sensor cord into the strain relief with
the sensor face to the inside of the plug as sembly. Place the sensor in the interstitial space between the primary
and secondary tanks approximately 1 in. above the tank bottom and securely tighten the strain relief to hold the
sensor and sensor cord into position. Remove the indicator box cover. Attach the indicator box to the PE mount-ing
plates provided on the tank with the 2 ea. #10 S. S. self-tapping screws. Attach the sensor cable to the control
box with small strain relief and connect wires per label in the box. Connect unit to 110 VAC per label in the box
using strain relief provided or other acceptable methods and test the unit. The indicator box will show a green
light when power is on and the sensor is not detecting a liquid. The light is a push to test light allowing the
operator to test for power outage or malfunction. If the green light goes out there are two possibilities. The
green light does not come on when the button is pushed. This would indicate a lack of power to the unit or the
light bulb is burned out. If the green light comes on when pushed, then a possible leak condition is indicated.
4.10 SIERRA SALES
FLANGE ADAPTERS
4.10.1 Standard flange adapters are constructed from PVC
or CPVC and may be purchased for solvent weld socket fittings or threaded fittings. Flange adapters for threaded
fittings are provided with loose male adapter to allow the customer to adjust adapter length and flange position
to match the piping at the installation. Refer to Figure 4.10 for an illustration of a flange adapter.
4.10.2 When installing the flange adapter in a solvent weld
socket fitting, cut the flange adapter to desired length and solvent weld the flange adapter with the proper solvent
cement in the desired position in a previously installed fitting. If the flange adapter is to be used in a threaded
fitting, install the male adapter into the fitting with Teflon 7 pipe sealant, cut the flange adapter to the desired
length, and solvent weld the flange adapter to the male adapter in the desired position with the proper solvent
cement.

Figure 4.10
| Previous Page | Document
Menu | Next Page|
SIERRA SALES
215-258-5602
Fax 215-258-5606
|